Current/voltage repeater KFD2-CD-Ex1.32 Connection Output EEx ia IIC ? J 1-channel Output EEx ia IIC 2- 1+ 24 V DC supply voltage Device installation permissible in 2- 1+ zone 2 Conversion of current/voltage or voltage/current Elevation/Suppression of the "life zero" Accuracy 0.1 % EMC acc. to NAMUR NE 21 Up to SIL2 acc. to IEC 61508 Option Option Current input Voltage input KFD2-CD-Ex1.32 R R m m Function J 50 mA The KFD2-CD-Ex1.32 transmits an electrical unit signal from the safe area to the hazardous area. The conversion of a current signal into a voltage signal 10- 9+ 11+ 10- 9+ 11+ and vice versa is possible. 10- 9+ 11+ 10- 9+ 11+ 7+ 8- Current input option Power supply Power Rail A current limit circuit in series to terminal 9 protects the device from Input Input damage. The max. voltage drop at the Current source Voltage input is DC 4 V, allowing for the connection of several KFD2-CD32- Ex1.32 repeaters due to the low voltage Composition drop in order to maintain multiple galvanically isolated outputs (signal duplication). Voltage input option The signal is transmitted to terminals 9 and 10 across an amplifier and the DC/DC converter within the allowable voltage range. A voltage limiter circuit protects the amplifier from incorrect input switching and overvoltage, but will draw current through a 50 mA fuse during operation. The fuse can be changed only by the manufacturer. Current output option The open circuit voltage is DC 24 V within the allowable supply voltage range at terminals 1 and 2. The max. load that can be applied is 850 ?. Voltage output option At least 20 mA is available within the allowable supply voltage range at terminals 1 and 2 which means that with 10 V output voltage, a load of at least 500 ? must be connected. Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group ? Tel.: Germany +49 621 776-0 USA +1 330 4253555 Singapore +65 67799091 Internet http://www.pepperl-fuchs.com 1 Release date 2006-03-01 15:06 Date of issue 2006-03-01 104204_ENG.xml Safe area or hazardous area, zone 2 Hazardous areaTechnical data KFD2-CD-Ex1.32 Supply Connection Power Rail or terminals 7+, 8- Rated voltage 20 ... 35 V DC Ripple within the supply tolerance Rated current current output: ≤ 50 mA ; voltage output: ≤ 20 mA Power loss 1.2 W Input Connection terminals 9+, 10-, 11+ Voltage drop U optional current input: approx. 4 V at 20 mA d Input current ≤ 100 μA up to 50 °C at 10 V Limit optional current input: input current: approx. ≤40 mA optional voltage input: input voltage: 12 V DC Transmission range optional current input: 0 ... 20 mA/optional voltage input: 0 ... 10 V Output Connection terminals 1+, 2- Current optional current output: 0 ... 20 mA/optional voltage output: ≤ 20 mA Voltage optional current output: 17 V at 20 mA/optional voltage output: 0 ... 10 V Load optional current output: ≤ 850 ? optional voltage output: output resistance ≤ 3 ? Transfer characteristics Deviation After calibration ≤ ± 0.1 % incl. non-linearity and hysteresis at 20 °C (293 K) Influence of ambient temperature ≤ ± 0.01 %/K Rise time < 10 ms Electrical isolation Output/power supply safe electrical isolation acc. to EN 50020, voltage peak value 375 V Directive conformity Electromagnetic compatibility Directive 89/336/EC EN 50081-2, EN 50082-2 Conformity Insulation coordination EN 50178 Electrical isolation EN 50178 Electromagnetic compatibility NE 21 Protection degree IEC 60529 Ambient conditions Ambient temperature -20 ... 60 °C (253 ... 333 K) Mechanical specifications Protection degree IP20 Mass approx. 100 g Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) Data for application in conjunction with hazardous areas EC-Type Examination Certificate BAS 02 ATEX 7203 , for additional certificates see www.pepperl-fuchs.com Group, category, type of protection ? II (1) G D [EEx ia] IIC (-20 °C ≤ T ≤ 60 °C) amb Voltage U 25.2 V DC 0 Current I optional current output: 93 mA 0 optional voltage output: 95 mA Power P 0.586 W 0 Supply Safety maximum voltage U 250 V (Attention! The rated voltage can be lower.) m Type of protection [EEx ia] Explosion group IIA IIB IIC External capacitance 2.9 μF 0.82 μF 0.107 μF External inductance 34.58 mH 17.04 mH 4.12 mH Internal capacitance 0 nF Internal inductance 0 mH Input Safety maximum voltage U 250 V (Attention! The rated voltage can be lower.) m Statement of conformity TüV 99 ATEX 1499 X , observe statement of conformity Group, category, type of protection, ? II 3 G EEx nA II T4 temperature classification Electrical isolation Input/output safe electrical isolation acc. to EN 50020, voltage peak value 375 V Output/power supply safe electrical isolation acc. to EN 50020, voltage peak value 375 V Directive conformity Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group Tel.: Germany +49 621 776-0 USA +1 330 4253555 Singapore +65 67799091 Internet http://www.pepperl-fuchs.com 2 Release date 2006-03-01 15:06 Date of issue 2006-03-01 104204_ENG.xmlTechnical data KFD2-CD-Ex1.32 Directive 94/9 EC EN 50014, EN 50020, EN 50021 Entity parameter Certification number 4Z6A5.AX FM control drawing No. 116-0129 Suitable for installation in division 2 yes Connection terminals 1, 2 Input I Voltage V 28 V OC Current I 93 mA t Explosion group A&B C&E D, F&G Max. external capacitance C 0.14 μF 0.43 μF 1.14 μF a Max. external inductance L 4.18 mH 16.83 mH 34.21 mH a Safety parameter CSA control drawing LR 65756-13 Control drawing No. 116-0132 Connection terminals 1, 2 Input I Safety parameter 28 V / 300 ? Voltage V 28 V OC Current I 93 mA SC Explosion group A&B C&E D, F&G Max. external capacitance C 0.14 μF 0.42 μF 1.14 μF a Max. external inductance L 3.1 mH 16.7 mH 34 mH a Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity and instructions have to be observed. For information see www.pepperl-fuchs.com. Application Used to drive I/P converters and valve positioners. Table: input/output options, type For options enclosed in parantheses, the transfer range for a base type is only partially used, i. e. 4 mA ... 20 mA from the base type 0 mA ... 20 mA. OUTPUT 0 mA ... 20 mA 4 mA ... 20 mA 0 V ... 5 V 1 V ... 5 V 0 V ... 10 V 2 V ... 10 V Ordering example: 0 mA ... 20 mA 0 2 - 9 12 - I Input 0 V ... 10 V, 4 mA ... 20 mA 1 0 10 - 13 12 N Output 4 mA ... 20 mA: 0 V ... 5 V 3 5 15 - - - P is code number 8 1 V ... 5 V - 3 - 15 - - U Type code: 0 V ... 10 V 6 8 21 - 15 - T KFD2-CD-Ex1.32.8 2 V ... 10 V - 6 - - - 15 Accessories Power Rail PR-03 Power Rail UPR-03 Power feed module KFD2-EB2... Using Power Rail PR-03 or UPR-03 the devices are supplied with 24 V DC by means of the power feed modules. If no Power Rails are used, power supply of the individual devices is possible directly via their device terminals. Each power feed module is used for fusing and monitoring groups with up to 100 individual devices. The Power Rail PR-03 is an inset component for the DIN rail. The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm x 2000 mm. To make electrical contact, the devices are simply engaged. The Power Rail must not be fed via the device terminals of the individual devices! Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group Tel.: Germany +49 621 776-0 USA +1 330 4253555 Singapore +65 67799091 Internet http://www.pepperl-fuchs.com 3 Release date 2006-03-01 15:06 Date of issue 2006-03-01 104204_ENG.xml |
|